| Start & Run Protection |
Two programmable overload trip curves: Class 5 – 30 Manual or automatic reset, remote reset available |
| Equipment Ground Fault |
Residual current method with adjustable trip delay |
| Phase Imbalance / Loss |
5 – 30% current imbalance between any two phases with trip delay |
| Short Circuit |
Trips at 10x unit current rating during run Checks for shorted load prior to each start |
| Shorted SCR |
Locks out on any single shorted SCR (defeatable) or shunt-trip on multi-SCR shorts / welded bypass |
| Electronic Shear Pin |
100 – 300% of motor FLA with trip delay |
| Motor Duty Cycle Protection |
Back-spin / coast-down, starts-per-hour or minimum time between starts lockouts Restart delay after a power failure |
| Pump-Flex™ Deceleration |
Begin decel 0 – 100% of line voltage Decel ramp 1 – 60 seconds End decel 0 – 1% of begin setting |
| Restart Delay Timer |
Programmable 1 – 999 seconds after loss of control power for staggered restarts |
| Metering |
Monitors phase current, ground current and motor thermal capacity |
| Comms |
RS-485, Modbus RTU protocol built in Up to 247 starters per link |
| Operator Interface |
Tactile feedback keypad Easy to read LED display with run and fault status indicators |
| Phase Rotation |
A-B-C, A-C-B or disabled |